 Safety relay
OA / OW 5669
* according to EN 50 205, IEC/EN 60 255, IEC 60 664-1 * with positively driven contacts * wash proof model as option * double and reinforced insultaion between contact sets according to EN 50 178 * low rated power consumption * high mechanical service life * compact size, small height * Approvals: UL, CSA, TUV approval: R 9012316
Applications: ZH1/457 press controls Switchgear for safety technology OA / OW 5669
Technical data
Relay type 1. 0 Relay coil 1. 1 Nominal voltage 1. 2 Nominal consumption 2. 0 Contacts 2. 1 Contact arrangement 2. 2 Contact material 2. 3 Rated insulation voltage AC V Switching voltage min./max. V 2. 4 Limiting continuous current A Switching current min./max. A 2. 5 Switching power min./max. VA Switching power min./max. W 2. 6 Switching capacity to IEC/EN 60 947-5-1 AC 15 AC V/A DC 13 DC V/A 2. 7 Electrical life 2) AC 230 V 6 A cos = 1 switching cycles 2. 8 Switching frequency max. switching cycles / s 2. 9 Response time / Release time ms 2.10 Contact force NO / NC cN 3. 3. 3. 3. 3. 3. 3. 3. 0 1 2 3 4 5 6 8 DC V W OA 5669 5, 6, 12, 20, 24, 48, 60, 110 0,7
1 NC / 1NO 2 changeover contacts, 1 No and 1 changeover contact AgCdO + 0,2 m Au; AgNi 10 + 0,2 m Au optionally + 5 m Au 250 AC/DC 10 / DC 250, AC 400 (AC/DC 100 mV / 60 V) 1) 2 x 5 (see operating voltage limit curve) 10mA3) / 8 (1 mA / 0,3 A)1) 3 / 2 000 (1 mVA / 7 VA)1) 3 / 200 (1 mW / 7 W) 1) (s. limit curve for arc-free operation) NC: 230 / 1 NC: 24 / 2 at 1 s On, 1 s Off > 1 x 105 AgNi 10 10 15 / 12 10 / 8 NO: 230 / 3 NO: 24 / 2 (s. contacts service life) > 2 x 105 AgCdO
Other Mechanical life switching cycles Temperature range C Degree of protection, housing Housing Vibration resistance Climate resistance Insolation according to IEC 60 664-1, EN 50 178 Rated insulation voltage AC V Contamination level Overvoltage category
50 x 106 - 40 ... + 60 mounted without distance (Ith = 2 x 5 A) IP40 / IP67 IEC/EN 60 529 wash proof Thermoplast GF, PA 10 ... 55 Hz; 0,35 mm amplitude; 5 g max. IEC/EN 60 068-2-6 40 / 060 / 04 (climate category); A/B/D IEC/EN 60 068-1 double and reinforced insulation 250 2 III
1)
Values for AgNi 10-contacts + 5 m Au
2)
10 A total current at t = 20C and coil voltage UN
3)
Typical values
All technical data in this list relate to the state at the moment of edition. We reserve the right for technical improvements and changes at any time.
OA/ OW 5669 / 25.02.03 d
Technical data
3. 8 Test voltage contact-coil (1 min) AC kV eff. contact-contact (1 min) AC kV eff. Transient volt. contact-coil (1,2 - 50 s) kV Clearance and creepage distances as per IEC/EN 60 730, IEC/EN 60 335 contact-coil mm contact-contact: mm 3. 9 Weight g 4 4 6 8 5,5 15
Standard variants
UN DC V 5 6 12 20 24 48 60 110 Voltage range DC V 4,0...8,0 4,8...9,6 9,6...19,2 16,0...32,0 19,2...38,4 38,4...76,8 48,0...96,0 88,0...176 Resistance at 20C 36 50 210 580 820 3 200 5 200 18 000 .16 461 462 463 468 464 465 466 467 Design version OA / OW .16 991 992 993 998 994 995 996 997 .12 980 981 982 987 983 984 985 986
Ordering example
O 5669.16 / Design version Contact arrangement .16 1 NC / 1 NO .12 2 changeover contacts .20 1 NO /1changeover contact Degree of protection A = IP 40 (solder line proof) W = IP 67 (wash proof)
Characteristics
M2869
1,6 1,4 1,2 UB UN 1,0 0,8
U B max. without load
4 2 10 7
Switching cycles
U B max. at 8A load
6 4 2 AgCdO 10 6 6 4 AgNi10 2 10 5 0 0,2 0,4 0,6 0,8 1,0 1,2 1,4 1,6
U B min.
0
20
40
60
80C
Ambient temperature
Switching capacity P [ kVA ]
Operating voltage limit curve
1,0 0,9 0,8 0,7 0,6
Contact service life (at tu = 20C)
260
V] M2871
M2642
Contact material AgNi
220 180 140 100 60 20 0
Reduction factor F
0,5 0,4 0,3
0,2 0,2
0,4 0,6 0,8 Power factor (cos ) Number of cycles = Number of cycles (ohmic) x reduction factor F
1
Switching voltage U [
0,2
0,4
0,7
2
4
6 8 10
Switching current I [ A ] safe switch-off, no standing arc arc max. 1 switching cycle / s
Reduction factor for inductive loads
Limit curve for arc-free operation (at tu = 20C)
M2870
10 8 6
Dimensions, pin configuration, connection diagrams
Connection for basic grid divensions 2,5 mm as well as 2,54 mm according to IEC/EN 60 097 and IEC 60 326 average
Dimensions, pin configuration, connection diagrams
Connection for basic grid divensions 2,5 mm as well as 2,54 mm according to IEC/EN 60 097 and IEC 60 326 average
Accessories
34
32
M2980
Fixing clip
Function modul
Relay socket
4
10
2x5 20,1 max. 31,5 7,5 max. 13
1 x 0,5
Socket ET 1415.021 ANR 0034 769 Fixing clip ET 1415.025 ANR 0034 770 Wire Fixing clip ET 1415.026 ANR 0047 726 Plastic
Relay socket ET 1415.041 ANR 0055571 with fixing clip WN 1415.902.790 Function modul ET 1415.911 ANR 0055909 - DC, with free-wheeling diode and red LED Function modul ET 1415.912 ANR 0055910 - AC/DC with green LED
E. DOLD & SOHNE KG * D-78114 Furtwangen
Postf. 1251 * Tel. (07723) 6540 * Fax (07723) 654356 * e-mail dold-relays@t-online.de * internet http: //www.dold.com


▲Up To Search▲   

 
Price & Availability of OA5669

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]